MODEL |
Nominal
Cooling
Capacity
(BTUH |
Rated*
Volts/
Hz/
Phase |
Amperes
(Cooling
Operations) |
Amperes
(Heating
Operations) |
CFM EVAP
High
Med
Low |
Fan RPM
High
Med
Low |
Fuse
Recommended (Time-Delay Type) |
Net
Weight
(pounds) |
Ship
Weight
(pounds) |
| AWC-12AV-*+ |
12000 |
230-208/60/1 |
5.7/6.3 |
|
510/460/400 |
1000/920/810 |
10 |
189 |
199 |
| AWC-12AA-*+ |
12000 |
115/60/1 |
11.2 |
|
510/460/400 |
1000/920/810 |
15 |
189 |
199 |
| AWC-18AV-*+ |
18000 |
230-208/60/1 |
8.2/9.0 |
|
625/560/480 |
1030/975/900 |
15 |
236 |
246 |
| AWC-24AV-*+ |
24000 |
230-208/60/1 |
11.3/12.4 |
|
780/700/630 |
1100/1050/1000 |
20 |
246 |
256 |
| AWC-30AV-*+ |
30000 |
230-208/60/1 |
14.5/16.5 |
|
780/700/630 |
1100/1050/1000 |
30 |
253 |
263 |
| AWC-36AV-*+ |
36000 |
230-208/60/1 |
18.5/20.4 |
|
1100/900/725 |
1550/1300/1050 |
30 |
282 |
307 |
| AWCH-12AV-*+ |
12000 |
230-208/60/1 |
5.7/6.3 |
18.5/16.8 |
510/400 |
1000/810 |
30 |
193 |
203 |
| AWCH-18AV-*+ |
18000 |
230-208/60/1 |
8.2/9.0 |
18.5/16.8 |
625/500 |
1030/900 |
30 |
240 |
250 |
| AWCH-24AV-*+ |
24000 |
230-208/60/1 |
11.3/12.4 |
19.1/17.4 |
830/780 |
1100/1000 |
30 |
250 |
260 |
| AWCH-30AV-*+ |
30000 |
230-208/60/1 |
14.5/16.5 |
19.1/17.4 |
830/780 |
1100/1000 |
30 |
257 |
267 |
| AWCH-36AV-*+ |
36000 |
230-208/60/1 |
18.5/20.4 |
37.2/34.9 |
1100/900 |
1550/1050 |
50 |
290 |
315 |
|
When ordering hazardous-duty units, must specify classification of area
(Class, Group(s) and Division/Zone) |
| *
When specifying model, substitute Group name (B, C, D, E, F or G) for the
asterisk (*) symbol |
| +
When specifying model, substitute Division/Zone 1 or 2 for plus (+) symbol |
| Information above applies Division/Zone 2 units; consult factory for characteristics of
Division/Zone 1 models. |
| Most units can be used without
modification at 220-200/50/1 at reduced capacity and with modification at 240-220/50/1 |
| Generally units have the same
height and width: 16-3/4" (43 cm) high by 26-1/2" (67 cm) wide
by 31" (79 cm) deep |